Mini presence detector / premium motion detector occy® Smart Home (24V) for Loxone, WAGO, Homematic, Comexio, etc. Mini motion detector with digital passive infrared technology (PIR)
24V mini presence detector motion detector occy® Smart Home for Loxone, Homematic, Comexio, WAGO, etc.
- Maximum installation height: 5m
- Output signal presence and light value: 10m active and passive
- No pull-up resistor required
- Power supply: 15-28V DC
- Ambient temperature 0-50 ° C
- IP 41
- Technology: digital passive infrared (PIR) sensor
- Presence detectors are particularly sensitive motion detectors for demanding indoor applications
Connect the motion signal to the digital input of the miniserver:
Connect the motion signal of the detector (BM) to one of the digital inputs I1 to I8.
The output of the presence detector is designed as a push-pull.
Connect the brightness value to the analog input of the miniserver:
Connect the light value signal of the detector (1-10V) to one of the analog inputs AI1 to AI4.
The presence detector outputs the light value as a 1-10V analog value. The more light there is in the room, the higher the tension. (0V = 0 Lux,
10V = approx. 1000 lux).
Pin assignment of the presence detector
Pin assignment of the presence detector | description | value |
24V | Supply voltage | 15 - 28 V DC |
GND | Ground / GND | 0V |
BM | Move | Detected movement = approx. supply voltage no movement = 0V max. 10 mA active / passive |
1-10V | Brightness value | 1-10V (0V = approx. 0 Lux, 10V = approx. 1000 Lux), (max. 10 mA) |
SLAVE + | SLAVE extension | Two-wire line |
SLAVE - | SLAVE extension |
Connections Loxone Miniserver
I1 - I8 | digital inputs | Internal input resistance: 10kOhm Max. 100 mA • 0-7.2 V corresponds to logic "0" • 7.0-8.2 V = switching threshold or |
AI1 - AI4 | Analog inputs | 0-10V DC, resolution 10 bit, internal input resistance: 10kOhm Can also be used as a digital input (24VDC) • <1V corresponds to logic "0" • 1 - 24V corresponds to logic "1" |
Q1 - Q8 | Digital outputs (Relay) | 250 V AC 5A at cos phi = 1, 30 V DC 5A (An auxiliary relay must be used for larger loads) |
AQ1 - AQ4 | Analog outputs | 0-10V DC, resolution 12 bit, max. 20mA output load |
Commissioning & test mode
After applying the supply voltage, every occy presence detector goes into a test mode. For 5 minutes the green LED always lights up when movement is detected. Then the LED goes out. In normal operation, the detector does not emit any light signals and also works completely silently.
Scope of delivery:
- Sensor head with
- Accessories for all 4 types of installation and
- 24V power pack for system connection.